Available object types and properties
Object types used in Aranet PRO BACnet server implementation are (1) Device object type, (2) Analog Input object type or (3) Analog Value object type (depends on the object type selection in “Compatibility options”).
Active Change-of-Value (CoV) subscriptions
Read-only
APDU timeout
Read-only
Application software version
Read-only
Daylight saving status1
Read-Write
Database revision
Read-only
Description
Read-only
Device address binding
Read-only
Firmware revision
Read-only
Local date
Read-only
Local time
Read-only
Location
Read-only
Maximum accepted APDU length
Read-only
Model name
Read-only
Number of APDU retries
Read-only
Object identifier
Read-only
Object list
Read-only
Object name
Read-Write
Object type
Read-only
Protocol object types supported
Read-only
Protocol revision
Read-only
Protocol services supported
Read-only
Protocol version
Read-only
Segmentation supported
Read-only
System status
Read-only
UTC offset2
Read-Write
Vendor identifier
Read-only
Vendor name
Read-only
The BACnet client system needs manual updates for daylight saving status. It doesn’t automatically update and can’t be adjusted through the Aranet PRO base web GUI, which operates on UTC time for its backend processes.
UTC offset must be updated from the BACnet client system as it is not being auto-updated and cannot be set using Aranet PRO base web GUI. BACnet UTC offset is inverse of common practice. If your UTC offset is -5 h of GMT, then BACnet UTC offset is +5 h. BACnet UTC offset is expressed in minutes, therefore convert the common UTC offset from hours to minutes.
Analog input / Analog value (measurement) object properties
CoV Increment
Read-Write
Description3
Read-only
Event state
Read-only
Object identifier
Read-only
Object name
Read-Write
Object type
Read-only
Out of service
Read-Write
Present value4
Read-only
Reliability
Read-only
Status flags
Read-only
Units
Read-only
9997 (proprietary) –– Time of last present value update
Read-only
9998 (proprietary) –– Date of last present value update
Read-only
Description is a combination of sensor hexadecimal UID, group name, sensor name, measurement type and unit, e.g., [500ACE] roomEnv Contact pulse meter pulses (pulses) where
[500ACE] –– hexadecimal UID
roomEnv –– group name
Contact pulse meter –– sensor name
pulses –– measurement type
(pulses) –– unit
Present value can be changed in case if Out of service value is set to “True”. It applies for both supported object types (AI and AV)
Last updated